Toshiba T300MVi Medium Voltage Standard Duty All Purpose Drive
Toshiba Updated: 2007-07-17The T300MVi Medium Voltage Adjustable Speed Drive is the most advanced drive in the industry. No other drive in the market offers this latest technology, a PWM 5-level design, which allows for a small footprint, reduced component count and ultimately a lower cost. The T300MVi can be retrofitted into any installation using the existing motors and is compatible with all power systems. In addition, it incorporates all of the latest safety technology making it one of the safest designs on the market.
T300MVi Standard Specifications
Voltage Class 4160 V
Drive Rating (A): 62 74 87 99 112 124 155 186 217 248 279 310 372 434 496 558 620
4160 Drive Output (kVA): 447 536 625 715 804 893 1116 1340 1563 1786 2010 2233 2680 3126 3573 4019 4466
Nominal HP 4160 V** 500 600 700 800 900 1000 1250 1500 1750 2000* 2250 2500 3000 3500 4000 4500 5000
Dimensions H x W x D (in) 104 x 74 x 44 104 x 122 x 44 104 x 164 x 50 104 x 174 x 50 104 x 222 x 50
Voltage Class 2400 V
Drive Rating (A): 64 75 86 97 107 129 150 172 193 215 269 322 376 430 504 537
2400 V Drive Output (kVA): 268 313 357 402 447 536 625 715 804 893 1116 1340 1563 1786 2010 2233
Nominal HP 2400 V** 300 350 400 450 500 600 700 800 900 1000 1250 1500 1750 2000 2250 2500
Dimensions H x W x D (in) 104 x 74 x 44 104 x 122 x 44 104 x 174 x 50 104 x 222 x 50
Power Requirements
Output Frequency (Hz) 0-120 Hz
Main Circuit Three phase 4160 V input isolation transformer 24 pulse design with input fused disconnect and vacuum contactor, IGBT output.
Control Circuit Integral to main transformer Includes 120 V and 460 V
Tolerance Voltage: 10% Frequency ? 5%
Control Specifications Input
Control Method Multi-level Pulse Width Modulated (PWM) Output Control
Frequency Precision 0.5% of max. output frequency: analog input, .01% digital input
V/F Control V/Hz, Sensorless Vector Control, Variable Torque, Closed Loop Vector Control, Constant Torque (Option)
Acceleration/Deceleration 0.1 ? 6000 sec.
Main Control Functions Soft Stall (Automatic load reduction control during overload)
Restart into a rotating motor
Main Protective Functions Current Limit, Overcurrent, Overcharge, Overload, Undervoltage, Overvoltage, Ground Fault, Cpu Error, Cooling Fan Abnormal
Data Transmission Ethernet; Optional Profibus, Modbus RTU, Modbus, TCP/IP, TOSLINE-S20, and DeviceNet available.
Overload Ratio 115% FLA for 60 seconds (2000HP 4160 110%)*
Interface
Liquid Crystal Display/ Electronic Operator (LCD EOI ) 4 x 20 Graphical Backlit LCD display. Ability to display multiple parameters on one screen. Software is flash upgradeable. Includes multi-function rotary encoder and ethernet PC interface.
LED Indications Run (Red) / Stop (Green), Remote / Local, Indication of inverter status
Keys Local / Remote, Monitor/Program, Run, Enter, ESC, Stop / Reset, Up, Down
Push Button Illuminated Interlock and Fault reset pushbuttons
Analog Outputs Eight selectable voltage or current output signals with programmable function
Analog Inputs Two selectable voltage or current input signals
Digital Inputs Eight digital inputs with programmable functions
Digital Outputs Six available digital programmable ouputs (One used internal to drive.)
Construction
Enclosure NEMA 1, IP20, IEC-529, Gasketed & Filtered
Panel Construction Free standing, front maintenance type, top or bottom access for motor and power cables
Cooling Forced air cooled with optional redundant fans
Color ANSI-61 Gray
Ambient Conditions
Ambient Temperature 0 ? 40°C, 32 ? 104°F
Humidity Max. 95% (No condensation)
Altitude 1000 m above sea level or less
Installation Indoor, No direct sunlight, protect for corrosive gases, explosive gases
Typical Applications Fan, Blower, Pump, Compressor, Extruder, options for submersible puming applications
Standards Electrical performance: NEC, ANSI
Components and Others NEC, NEMA, UL
**Typical HP rating of a 4 pole motor. Contact factory for applications on constant torque loads.
T300MVi Engineering Spec
T300 MVi EOI Manual
T300 MVi Instruction Manual
Wi Tool - How to Save Traceback Files
Wi Tool Installation Note
Wi Tool Instruction Manual 6F3A4508-0
T300MV Medium Voltage Drive Brochure
Related Manuals
Toshiba W7 Low Voltage Variable Torque Water/Wastewater Drive
Toshiba MTX NEMA 3R MV Severe Outdoor Drive
Toshiba AS1 Low Voltage Standard Duty Integrator Drive
Toshiba G3+ Low Voltage Severe Duty Specialty Drive
Toshiba nC1 Low Voltage Standard Duty Micro Drive
Toshiba S11 Low Voltage Standard Duty Micro Drive
Toshiba Q7 Low Voltage Variable Torque HVAC Drive
Toshiba HX7 Low Voltage Standard Duty Specialty Drive
Toshiba H7 Low Voltage Standard Duty Industrial Drive
Toshiba G7 Low Voltage Severe Duty Industrial Drive
Toshiba G9 Low Voltage Severe Duty Industrial Drive
Hitachi SC-OPE 3H/3I Operator Interface and Networking Devices